GB51171-2016通信线路工程验收规范(英文版)
上QQ阅读APP看本书,新人免费读10天
设备和账号都新为新人

3.9 Distribution Frame Examination

3.9.1 Examination of optical cable distribution frame shall meet the following requirements:

1 For the distribution frame,the coating on its surface shall be smooth,evenly-colored,without any sagging or exposure;its metal ware shall be free from any burrs or rusts.The labels on the frame shall be complete,clear,accurate and durable.

2 The frame shall have all the function modules completely installed.

3 Insulation resistance between earthing device and frame rack,as well as high voltage tolerance,shall comply with the requirements of current professional standard Optical Fiber Distribution Frame YD/T 778 or the design requirements.

3.9.2 Connector examination shall meet the following requirements:

1 Connector shall be free from any stain,burr,crack,losing-off,deformation or shift and shall be clearly marked.

2 Connection and disconnection between connector plug and adapter shall be smooth,easy,firm and flexible to ensure normal functioning.

3 Optical fiber cables of connector shall be smooth and glossy,without any impurities or damage,and with legible printing and required colors.

4 Insertion loss and return loss shall meet the design requirements.

3.9.3 Cable distribution frame examination shall meet the following requirements:

1 For the cable distribution frame,its coating on the surface shall be smooth,evenly-colored,without any sagging or exposure;the labels on the frame shall be complete,clear,accurate and durable.

2 Metal ware shall have smooth coating(plating)without any obvious difference,scars,rusts or flakes.

3 Plastic ware shall be evenly-colored,without any obvious difference,crack or scar.

4 Fastener shall be provided in full and firmly installed,with its frame and connector bars horizontally and vertically aligned.

5 The labels on the frame shall be complete,clear,accurate and durable.

6 Insulation resistance between protective earthings,between any independent connectort-erminals,between any connector terminal and metal fastener,as well as overvoltage or overcurrent protectors shall comply with the requirements of current professional standard Main Distribution Frame YD/T 694.